CHICAGO CODE
COOPER LIGHTING
COOPER LIGHTING - SURE-LITES
®
DIMENSIONS
6.5”
[165mm]
11.5”
[292mm]
Dual Voltage input,
120/277 VAC, 60 Hz
Die cast aluminum housing
Two 6V 12W MR16 lamps
Sealed Lead Calcium
Powder Coat Finish
Watchguard EMS
Self-Diagnostic System
Photocell Test Switch
(requires accessory LASER
for activation)
UL924 Listed, Damp
location listed, Life Safety
NFPA 101, NEC/OSHA,
most state and local codes
City of Chicago Fire Code
DESCRIPTION
The Sure-Lites CHEL Emergency Light
provides a distinct solution to any
emergency lighting application.
Constructed of die cast aluminum, the
CHEL presents not only a unique shape
and design but also provides dependable
strength and durability. The two, fully
adjustable, high efficiency 12W MR16
lamps provide maximum path of egress
performance. The standard Watchguard
EMS self-diagnostic system meets NFPA
101 testing requirements providing
assurance that the unit is working
properly at all times. The Sure-Lites
LASER test feature allows remote, 30
second confidence testing of the
emergency light upon demand.
CHEL SERIES
Die Cast Aluminum
CHICAGO CODE
EMERGENCY LIGHTING
4.0”
[102mm]
ORDERING INFORMATION
SAMPLE NUMBER: 6CHEL1SD
Family
CHEL1=Architectural
Emergency
Light
CHEL1
Housing
Finishes
Blank=Silver
BK=Black
WH=White
Accessories (order separately)
LASER=Key Chain, Red Laser Pointer
(activation tested at 30 feet)
SD
SD=Self Diagnostics
(Standard)
ELECTRICAL RATINGS
Model DC Voltage 1 1/2 Hours
CHEL1SD 6 24
Rated Wattage to 87 1/2% of Rated D.C. Voltage
Lamp Information
Type Wattage Number Spacing
1
MR16 12 29-140 50'
Options
TDM=Time Delay Monitor
(1)
The "Rule of Thumb" spacing guidelines are designed to achieve 1 foot-candle average and 0.1 foot-candle minimum with a 40:1
maximum/minimum ratio. The corridor used is 100 feet long, 9 foot ceiling with a 6 foot wide walkway and 3 foot path of egress.
The reflectances are 80% ceiling, 50% walls and 20% floors. The fixture mounting height is 7.5. Cooper Lighting assumes no responsibility
for local requirements or specific project variables. This is a guideline to be used as a design aid, not as guarantee of any code compliance.
Self-Diagnostics
The self-diagnostic unit will automatically
perform all tests required by UL924 and NFPA
101. The system indicates the status of the unit at
all times using the LED indicator near the test
switch on the side of the unit. A 90 minute battery
power (emergency mode) simulation test will
occur randomly once every six months.
A 30 second battery power simulation test will
occur every 30 days.